93.gif (11943 bytes)

 
【Summary】
  GGD low-voltage switch board is suitable for such electric users as transformer substation , power plant , industrial enterprise ,etc.. Exchange 50Hz, amount working voltage 660V and following, specified job electric current heavy distribution in 3150A system light as power and whom electric energy , distribution of equipment change , assign use most.

【Normal service condition】
1、Ambient air temperature is not higher than +40 degrees Centigrade , it is not low- 5 degrees Centigrade, and its average temperature is not higher than +35 degrees Centigrade in 24 hours.
2、The air cleans, the relative humidity does not exceed 50% when the maximum temperature is +40 degrees Centigrade; Is it have higher humidity to allow at low temperature, for example +20 degrees Centigrade 90%; Allow because temperature may produce and congeal to reveal while changing.
3、The height above sea level does not exceed 2000m .

【Install the size in appearance】
A
B
C
D
600
600
450
556
600
800
450
756
800
600
650
556
800
800
650
756
1000
600
850
556
1000
800
850
756
1200
800
1050
756
【Structure characteristic】
1、
The cupboard shelf of GGD low-voltage switch board adopts 8MF cold curved section steel part to weld and assemble . The spare part of the switch board is designed according to the principle of the module , external dimension and turning on the size of hole to press the basic modulus E =20mm change.

2、The cupboard door is connected with cupboard body with the pivot type activity hinge, install , dismantle it conveniently. Hem place of door inlay have one mountain rubber piece , can prevent door and direct collision , cupboard of body from, have improved the grade of shelter of the door too.

3、Switch board at the body, lay both ends have trough holes of heat dissipation , after the electric apparatus component generates heat in the cupboard, temperature rises, the hot air is discharged through the top trough hole, and the cold air is being supplemented by the underpart trough hole constantly, make sealed cupboard body from bottom to top , form one natural ventilation dish , achieve the goal of dispelling the heat.

4、The grade of shelter of the cupboard body is IP30.
 
【Users should offer the following materials while ordering 】
· The systematic picture of a low-voltage once of electricity distribution room, indicate the scheme serial number selected for use.
· Return circuit principle picture or wiring diagram two times.
· The permutation picture of the switch board and level of the electricity distribution room are fixed up and pursued .
· Detail specification and quantity very containing electric equipment in each switch board .
· The job electric current of the main bus bar or material specification.
· Membrane color that the switch board surface is painted.
 
【Technical parameter】
Type

rating
voltage
(V)

rating
electric current
(A)
Amount shorts out Turn on and break the electric current
(kA)
Amount shorts out Tolerance electric current
(I s) {kA)
Specified peak value Tolerance electric current
(kA)
1
380
A
1000
15
15
30
B
630
C
400
2
380
A
1600
30
30
63
B
1000
C
630
3
380
A
3150
50
50
105
B
2500
C
2000
 

Address:6 XIYUAN Road
86-0512-88871353
    86-0512-88871356
Fax:86-0512-88871360
Zip Code:215011

     版权所有:苏州正环电气有限公司  制作维护:苏州创景网络有限公司