93.gif (11943 bytes)

 
【Summary】
  Exchange removing type three phases of new generation of switchgear department of the metal armor to exchange 50Hz in the Model KYN28-12 family, specified voltage 3. The distribution device of 6-12kV, extensively suitable for segmenting in the single bus bar and single generatrix the system, complete sets in one of using as accepting and distributing electric energy. Switch device design , making according with IEC293-96 and GB3906-97 and DL/T-404-97 standard.

 
【Structure characteristic】
1、Adopt new-type ZN12 , VD mouth , VS1 vacuum circuit breaker, have small , light , such characteristics as performance is reliable .
2、Cupboard body is it is it aluminize zinc to be board curved to make panel and modulus assemble to import to adopt, the commonability is strong, but make wantonly up , and anti-oxidant ability is strong, firm among cupboard body and the car , all kinds of door reliable Fang locks the device by mistake , easy to operate and flexible.
3、China's putting type, double-deck formula overall arrangement, it is simple , reliable to operate; There is abundant space in the cable room, can link many roots cable , it is convenient to install , maintain .
4、The handcart interchangeability is good.
5、Have temperature , automatic control system of humidity , has guaranteed the equipment runs reliably.
 
【Normal service condition】
·The temperature upper limit of ambient air is +40 degrees Centigrade, lower limit- 10 degrees Centigrade
·Above sea level not to exceed 1000m
·The relative humidity is not greater than 90% (+25 degrees Centigrade)
·The ambient air should not receive the vapor , the obviously polluting of corrosivity or the flammable gas,etc.
·There is no regular violent place to shake .
·The earthquake intensity does not exceed 8 degrees
 
 
【Users should offer the following materials while ordering】
·All types of the products, including scheme number of the main circuit and auxiliary circuit scheme number .
·Systematic picture of the main circuit.
·Electric principle picture of auxiliary return circuit .
·Components and parts inventory in the cupboard.
·Other special demands .
 
【Technical parameter】
Serial number
Project
Unit
Data
1
Specified voltage
KV
3.6-12
2
Insulating level of amount
1minThe worker is able to bear pressing frequently
KV
42
The thunder and lightning is assaulted and able to bear pressing
KV
75
3
Rated power
Hz
50
4
Specified electric current of main bus bar
A
630、1250、1600、2000、2500、3150
5
Amount is able to bear receiving the electric current (4S ) in short-term
KA
16、20、31.5、40
6
Tolerance electric current of specified peak value
KA
40、63、80、100
7
Grade of outer cover shelter
IP4X
 

Address:6 XIYUAN Road
Tel:86-0512-88871353
    86-0512-88871356
Fax:86-0512-88871360
Zip Code:215011

     版权所有:苏州正环电气有限公司  制作维护:苏州创景网络有限公司