93.gif (11943 bytes)

 
【Summary】
  GCK low-voltage taking out type switch board is suitable for exchanging 50Hz, 660V and the following three-phase Line five make power transmission and distribution system. Use as what the power plant , transformer substation , worker's vast enterprise and the skyscraper of the power system are controlled by the electricity , feed , illumination and motor.

  This product accords with IEC 439-1<Low-voltage complete set of switch equipment and controlling the equipment>;GB7251.1—1997<Low-voltage complete set of switch equipment and controlling the first part of equipment, test and test the complete sets with some patterns in pattern>and ZBK36001-89<Low-voltage taking out type complete set of switch equipment>Standard.

  GCK low-voltage taking out type switch board , adopts advanced assembling the structure and making the unit up , person who take out make up unit pile load with in the compartment , it protects the grade as IP30 on close metal cupboard body, advantage of have safe , reliable , compactness , convenient , flexible etc.

  GCK low-voltage switch board , has special-purpose measurement cupboards, can meet the electric power system to the low-voltage demand that measures .
  GCK low-voltage switch board , has special-purpose static condenser cupboards, as compensating the using of inactive power.

【Normal service condition】
1、Ambient air temperature high level cadre +40, lower than- 5, and 24 hours its average temperature is not higher than +35 degrees Centigrade .
2、Air clean, relative humidity when +40 of maximum temperature , exceed 50% ; In lower temperature, allow to have higher humidity, for example: +20 degrees Centigrade is 90% at; Allow because temperature change may produce congeal and revealing.
3、The height above sea level does not exceed 2000m .

【Install the size in appearance】
A
B
1000
600
1000
800
1200
1000
 
 
【Structure characteristic】
Body structure of the cupboard:
  GCKl low-voltage switch board of taking out etc. for all assembling type combining structure, the basic skeleton adopts the special-purpose material to assemble , cupboard body skeleton , part external dimension turn on hole size press the basic modulus E =20mm change.
  Fasten because of all structure of frame with screw connection , is it weld out of shape with stress to avoid, have improved the precision.
  Every cupboard body is separated into three parts, namely main bus bar room for the horizontal bus bar to run through on the top , the part in the front is separated into a small room of several function units with the baffle , the height is 1760mm after making up, it is the cable room partly to be following, contain the support in the room , is used for laying and passing in and out the cable.
  
Having set up the vertical bus bar behind the small room of the taking out type function unit, the vertical bus bar utilizes the branch bus bar and horizontal bus bar to link, each taking out type function unit, it is linked in the position and vertical bus bar that putting through. The cupboard carries the metal which is equipped with the ventilator and seals the board; The top is while needing to pass in and out the line, adopt and seal the board insulatingly, the bottom seals the board for the metal, wash and strike and leave the hole on it, pass in and out with the sharp cable.

Taking out type systematic structure:
  The electric apparatus component of each function unit is installed on a drawer , can make the whole unit break away from the cupboard body , maintenance is safe , convenient.
  The drawer is put in the wide cupboard body of 600mm, there is " separating " , " test " , " put through " in three seats. The power in the light room of drawer enters the thread side and is equipped with the valve, the drawer is being " tested ", " put through " to the position, the valve is opened automatically, is " separating" the position, the valve is being closed automatically.
  Small room door and return circuit main switch have interlock , close main switch little room door can be opened, can also unblock and open the door under the special circumstances.
  
The main return circuit electric current is and following in 100A, the height of small room is 220mm; 45A and the following return circuit , can generally install two drawers side by side . The height of small room of return circuit of 200A , 400A is generally 440mm, the small room of the return circuit of 600A is generally 660mm.

Bayonet systematic structure:
  Main return circuit electric current>, at the 630A , adopt frame posture circuit breaker of structure of injecting etc. , is it push into spiral shell's pole finish putting through and disconnection with generatrix to sway with gear shift.
  The regular installation of other electric apparatus components besides main switch is in the small room.

Systematic structure of regular type:
  Measuring the unit and static condenser cupboard, adopt the regular type to be installed, all electric apparatus components are installed on the crossbeams or mounting plates of the switch board .

 
【Users should offer the following materials while ordering】
· A return circuit scheme and systematic picture one-way;
· Return circuit principle picture or wiring diagram two times;
· The permutation picture of the switch board and level of the electricity distribution room are fixed up and pursued ;
· Detail specification and quantity containing various kinds of electric equipment in each switch board ;
· Offer the job electric current of the horizontal bus bar or material specification ;
· Membrane color that the switch board surface is painted.
 
【Technical parameter】
Serial number
Project
Norm
1
Working voltage of amount(V)
Exchange380
2
Insulating voltage of amount(V)
660
3
Frequency(Hz)
50
4
Specified electric current (A)
Horizontal bus bar
1600、3150
Vertical bus bar
630
The main circuit touches the head and connects the plug-in package
200、400
The auxiliary circuit touches the head and connects the plug-in package
20
The largest electric current of feed circuit
400
Receive the electric circuit
1000、1600、2000、2500
5
Amount is able to bear receiving the electric current in short-term (kA)
Virtual value
50
Peak value
105
6
Insulating level of amount: The worker 50Hz frequently . 1min(V)
2500
7
Control the capacity of the motor (kW)
0.45-155
8
Mechanical life-span (time)
500
9
Protect the grade
IP30
10
Accord with the standard
IEC439.1、GB7251.1
 